Skip to main content

Powerful products from BBC Cellpack Smart Energy for the grid of tomorrow

As a manufacturer and service provider for sustainable solutions in network levels 5 to 7, we know the requirements and needs for corresponding products from many years of experience.

Comprehensive Smart Grid Solution

With SGIM by BBC Cellpack Power Systems, low-voltage grids can be visualized in an instant and aligned to future requirements. 

Easy: The state of the low-voltage grid can be visualised quickly, easily and cost-effectively - current data already from the very first day! 

Reliable: Regardless of costly infrastructure due to web-based solution - implemented with proven industrial technology and certified according to the most recent standards, including cyber security. 

Persuasive: A comprehensive package with low investment costs and operating costs. A system that adapts to the development of the smart grid and grows with the needs of customers.

Key arguments for SGIM

All-in-one solution with tried and tested hardware, transmission, visualisation and data management can monitor up to 10 low-voltage connections per unit, both 3-phase and 4-phase. Voltage, current, mains frequency, and phase angles are measured as a standard feature. Furthermore, expandable additional functions can be added using various interfaces. The measured data is automatically transferred to a portal server with archiving function and can thus be easily evaluated. Moreover, the SGIM solution is compatible with several well-known network analysis systems and asset management applications. The unit can be easily installed on a 185 mm busbar system or retrofitted without interruption. The investment and operating costs are low and the scalability of the system ensures investment protection.

Highlights

  • All-in-one solution with tried and tested hardware, transmission, visualisation, and data management

  • If required, 3-phase and 4-phase monitoring of up to 10 low-voltage connections per unit is available

  • Voltage, current, mains frequency and phase angles as an integrated standard feature, and extensible

  • easy availability of measured data on portal server with archiving function

  • Interruption-free, simple (post-)installation on 185 mm busbar systems

  • low investment and operating costs

  • Scalable 

For technical support:

André Lüscher
Sales SGIM
Email
+41 56 619 88 46

 

Contact sales office

Persons

 

Downloads

SGIM-Broschüre

 

Other products

from BBC Cellpack Power Systems

Technical data

Dimensions

  • Design: Format of a low and high-voltage switchgear combination for 185 mm busbar system

Power supply

  • Input voltage: 1 x 230 V (L1), (100 to 240 V), 50 Hz

  • Power consumption: <25 VA

Voltage measurement

  • Measurement category: IV

  • Measuring method: Lx -N

  • Resolution: 0.01 V

  • Measurement range: 1.5 x Vrated (max. 300 V)

  • Accuracy: Class 0.5

  • Measurement functions: Average value, minimum, maximum

  • Minimum averaging time: 60 s

Measurement of current

  • Measuring method: with SGIM-Rogowski sensor set (RC) or current transformer (CT) 3 or 4-wire

  • Resolution: 0.01 A (depending on RC or CT)

  • Secondary rated current: 1A

  • Measurement range: 1.7 x Irated (up to 15 kA)

  • Accuracy: Class 0.5 + accuracy RC or CT, class 1.0 with SGIM-Rogowski sensor set

  • Measurement functions: Average value, minimum, maximum

  • Minimum averaging time: 60 s

Mains frequency measurement

  • Resolution 0.01 Hz

  • Measurement functions: Average value, minimum, maximum

  • Minimum averaging time: 60 s

Power measurement

  • Measurand Apparent, active, and reactive power

  • Measurement functions: Average value, minimum, maximum

  • Minimum averaging time: 60 s for active power, 900 s for apparent and reactive power

Energy measurement (electrical work), consumption and feed

  • Measurand Apparent, active, and reactive power

  • Measurement functions: Average value, minimum, maximum

  • Minimum averaging time: 60 s for active power, 900 s for apparent and reactive power

Power quality measurement

  • Measurand THD voltage, THD current

  • Measurement functions: Average value, minimum, maximum

  • Minimum averaging time: 900 s

Additional functions (supply for external additional devices)

  • Voltage: +12 V or +24 V

  • Max. Output: 5 W

  • Sensors: Temperature and humidity

Connectivity via various modules

  • I/O module - 2 relay contacts (G5SB): Operating voltage 250 VAC, CAT II, max. operating current 3 A, 8 x digital input (0 to 12 V, 5 mA), debounce time 10 ms

  • Internet gateway: LAN, WLAN, LWL, UMTS, PLC

  • Communication: Bluetooth, Modbus, RS485

Standards:

  • Conformities: EMC Directive 2014/30/EU (4 kV / 8 kV), Low Voltage Directive 2014/35/EU, RED 2014/53/EU, RoHS 2 Directive 2011/65/EU

  • Measurement technology and communication: EN 61557-12 (P, Q, S, E, U, I, f, RMS), IEC 60870-5-104 or IEC 61850, IEC 61000, EN 61326, EN 61010